Data on Data Centers

Public data on the environmental footprint of data centers: air sensor readings, noise measurements, water use, electricity use and carbon dioxide estimates, and updates on legal, regulatory and scientific developments.

What's new

    Daily air readings

    DEQ sensor location (grey lines) and EPA's regulatory monitor (dark dashed line) for background at Broad Run HS (PM2.5), and Broad Run HS (NO2) and James S. Long Park (NO2). EPA has no CO monitor in either county and thus has no reference. Sensor data last updated on .

    Or drag across the strip under the chart to pick any period. Click the strip to reset.

    Gaps in a line are periods when the sensor was not in service. July 16-20, 2026, when Canadian wildfire smoke covered the region, is left out by default; toggle "Show smoke days" on the upper right hand corner to view data for those days.

    Insights

    • PM2.5 levels near the data centers are generally consistent with the EPA's regulatory monitor, though with some variability.
    • Less consistency between NO2 sensor readings and the EPA monitor.
    • Not possible to compare CO sensor readings with the EPA monitor.
    • PM2.5 readings from July 16-20, 2026, are consistent with Canadian wildfire smoke reported across the region (Capital Weather Gang; Potomac Local). All six sensors and the EPA monitor peaked on July 17 with daily means of 68 to 96 µg/m³ at the sensors and 171 µg/m³ at the EPA monitor, compared with a typical daily mean of about 5 µg/m³ on other days. A local source, such as the backup generator run reported at Vantage VA2 in Sterling on July 16-17 (Virginia Mercury), would raise readings at sensors downwind of it rather than at every sensor at once. These days are not shown on the chart by default; toggle "Show smoke days" to view or hide them.

    Further analysis would need to be conducted to formally test these and other patterns.

    Sensor locations

    From hourly data (not the daily averages above). Units: PM2.5 µg/m³, NO2 ppb, CO ppm.

    LocationCountyFromToPM2.5 meanPM2.5 peak hourPeak dayNO2 meanNO2 peak hourCO mean

    Instruments

    • DEQ sensors: Kunak AIR Pro, made by Kunak (Spain), listed in DEQ's reports as "APEX/Kunak AIR Pro." PM2.5 is measured with a laser optical particle counter, which counts and sizes particles and converts the counts to mass using an assumed particle density. NO2 and CO are measured with electrochemical cells.
    • Regulatory monitors at Broad Run High School: Teledyne T640x for PM2.5 and Teledyne T500U for NO2 (as labeled in DEQ's August 7, 2026 report). Both are EPA-designated Federal Equivalent Method (FEM) instruments.
    • Agreement between sensors and regulatory monitor (DEQ, August 7, 2026): at Broad Run High School, where a sensor was placed next to the regulatory monitor, hourly PM2.5 tracked the monitor reasonably well (R² of 0.73 for the first sensor unit, March 3 to April 8, 2026, and 0.84 for the second unit from April 8; DEQ notes the July 17 wildfire smoke strongly influences the second figure). NO2 tracked it poorly (R² of 0.49 and 0.17). There is no regulatory CO monitor in Loudoun or Prince William County, so CO readings could not be checked locally.
    • DEQ states that the sensors are not regulatory instruments and cannot be used to determine whether the area meets the National Ambient Air Quality Standards (NAAQS). DEQ's reports describe no correction factor applied to the sensor data, and none is applied here.

    Notes

    • Air sensors: Virginia DEQ Data Center Air Monitoring Project (Kunak AIR Pro; see Instruments above), hourly readings summarized to days in Eastern Standard Time. Daily means calculated for days with at valid measurements for at least 18 hours; the highest-hour view shows the largest single hourly reading that day.
    • Reference: EPA Air Quality System daily summaries for the regulatory monitors. PM2.5 uses the hourly-derived daily mean where at least 18 hours exist, otherwise the 24-hour filter value.
    • Heritage Farm Museum is cut off after May 28: its PM2.5 went flat near zero before DEQ pulled the sensor.
    • The two newest Prince William locations have only about ten days of data.